Effect of Operating Temperature on the Perfomance Effectiveness of Cooling Tower in a Phosphoric Acid Concentration Unit
DOI:
https://doi.org/10.31004/anthor.v5i5.1474Keywords:
Cooling Tower, Effectiveness, Range, Approach, Phosphoric AcidAbstract
Cooling towers play a crucial role in industrial cooling systems by reducing water temperature through heat transfer and evaporation. Their performance significantly affects process efficiency, particularly in phosphoric acid concentration units. This study aims to evaluate cooling tower performance based on operating temperature and to compare actual operating conditions with design specifications. Primary data inlet and outlet water temperature, wet-bulb temperature, humidity, and water flow rate were collected through direct field observation and analyzed using the range, approach, effectiveness, and heat loss parameters. The results show a significant decline in actual performance relative to the design condition: the actual range was 5.7°C, lower than the design value of 14°C, while the actual approach was 13.4°C, higher than the design value of 6°C. Cooling tower effectiveness reached only about 30%, far below the design value of 70%, indicating a substantial reduction in heat-transfer capability. This decline was attributed to scaling on the water distribution system, uneven water distribution across the fill media, and reduced fan performance. These findings provide a basis for evaluating cooling tower operating parameters and can support efforts to improve cooling-system efficiency in the phosphoric acid industry.
References
Afshari, F., & Dehghanpour, H. (2018). A review study on cooling towers: Types, performance, and application. NSP, 1–10.
Ahluriza, P. (2022). Review pengaruh range dan approach terhadap efektivitas cooling tower di PT. IP. August. https://doi.org/10.23887/jptm.v9i2.34899
Bamimore, O. T., & Enibe, S. O. (2021). Parametric effects on the performance of an industrial cooling. 7(4), 904–917.
Cahya, A., Pratama, P., Mugisidi, D., & Heriyani, O. (2026). Seawater evaporation using natural flow solar still. 13(1), 137–143.
Engineering, M. (2025). Evaluation of cooling tower performance in a process plant. 11(10), 276–289. https://doi.org/10.56201/ijemt.vol.11.no10.2025.pg276.289
Ghamdi, A. S. Al, Mahmoud, A. M., Ahmed, S., Abdulaziz, B., & Rajhi, A. (2023). Performance analysis of a cooling tower system used for cooling hot thermal distillate from a desalination system under severe climatic conditions. Desalination and Water Treatment, 315, 24–31. https://doi.org/10.5004/dwt.2023.30078
Ghoddousi, S., Anderson, A., & Rezaie, B. (2021). Advancing water conservation in cooling towers through energy–water nexus. 5(3).
Hensley, J. C. (2003). Cooling tower fundamentals. https://doi.org/10.1201/9780203912492.pt4
N. A. (n.d.). Analisis pengaruh temperatur ambient terhadap kinerja cooling tower unit 2 berdasarkan evaluasi range dan approach pada PLTGU PT Mitra Energi Batam [PDF].
Naik, B. K., Choudhary, V., Muthukumar, P., & Somayaji, C. (2017). Performance assessment of a counter flow cooling tower: Unique approach. Energy Procedia, 109, 243–252. https://doi.org/10.1016/j.egypro.2017.03.056
Navarro, P., Ruiz, J., Kaiser, A. S., & Lucas, M. (2023). Effect of fill length and distribution on the thermal performance of an inverted cooling tower. Applied Thermal Engineering, 231, Article 120876. https://doi.org/10.1016/j.applthermaleng.2023.120876
Nurisman, E., Syafira, Z., & Shania, F. (2020). Studi kinerja cooling tower unit amoniak dan urea pada sistem utilitas industri petrokimia. Jurnal Teknik Kimia, 26(1), 37–41. https://doi.org/10.36706/jtk.v26i1.9
Rahayu, R. D. (2025). Analisis performa cooling tower T-1201A dan T-2211A/B pada unit utilitas Departemen Produksi 1A PT Petrokimia Gresik. 11(9), 333–342.
Rahman, A. M. (2022). Analisis kinerja cooling tower menggunakan metode range dan approach di PLTU Asam-Asam. 4(2), 15–27.
Tower, C., Analysis, P., Range, U., & Method, A. (2025). Journal la multiapp. 6(4), 785–798. https://doi.org/10.37899/journallamultiapp.v6i4.2306
Wahyu, S., Mustain, A., & Rizky, M. A. (2023). Analisa perhitungan efisiensi cooling tower 32 T 821 pada Utilitas II Produksi II B PT Petrokimia Gresik. DISTILAT: Jurnal Teknologi Separasi, 9(1), 114–119. https://doi.org/10.33795/distilat.v9i1.520
Downloads
Published
How to Cite
Issue
Section
License
Copyright (c) 2026 Kaori Amelia Putri, Izran Febrian, Naomi Jeris Simanjuntak, Azafilmi Hakiim

This work is licensed under a Creative Commons Attribution-ShareAlike 4.0 International License.